Lightning Arrester

Short Description:

Lightning Arresters is an important protector in electric power system,which be used to pretect the main electric devices against Over-Voltage.Zinc Oxide Arresters adopts zinc oxide varistors with good volt-ampere characteristic nonlinearity as its core,which show high resistance when system nomal boltage,the current only have microamps level; when over voltage,the current that through zinc oxide varistors run up, can fast release the power of over-voltage,thus limit extent of over-voltage, meanwhile,zinc oxide varistor also have these features of large flow capacity, fast response speed,fast response speed,good protection performance and so on. MOAS of this are designed for export.The perfomance of the arresters meets the requirements of Standard IEC60099-4.


Product Detail

Product Tags

Features

1.Reliability and excellent protection based on years of experience and expertise in surge protection.

2. Good anti-moisture capability, resistant to pollution.

3. GIS metal oxide surge arrester, composite metal oxide surge arrester and porcelain metal oxide surge arresters are available.

4. Long life and lightweight.

5. Easy installation and maintenance.

6. Good sealing capability to ensure reliable operation.

7. High energy absorption ability.

Application

1.Ambient tempreturature within the range of -45℃ to +40℃

2.Altitude can up to 2000m

3.A.C. voltage frequency 48-62Hz

4.Product Surface temperature no more than 60℃ in the sun

5.Ice thickness in no more than 2cm

6.Maxium wind speed 35m/s

7.Eqrthquake intensity: 7 degree and below

Technical Parameter Of Lightning Arrester

Rated Voltage

12KV

24 KV

36 KV

42 KV

Rated frequency

48~62Hz

48~62Hz

48~62Hz

48~62Hz

Continuous operating voltage

9.6KV

19.2 kV

28.8 kV

33.6 kV

Nominal discharge current

10KA

10kA

10kA

10kA

Power frequency reference voltage

12KV

24 kV

36 kV

42 kV

Lightning impulse residual voltage

36KV

72 kV

108 kV

126 kV

Steep current impulse residual voltage

41.5KV

82.8 kV

124.2 kV

145 kV

Switching impulse residual voltage

30.6KV

61.2 kV

91.8 kV

107 kV

Rectangular current withstand 2000μs

250A

250A

250A

250A

High current withstand 4/10μs

100KA

100kA

100kA

100kA

Line discharge class

1

1

1

1

Partial discharge

10pC

10pC

10pC

10pC

Creepage distance

351mm

655mm

894mm

1083mm

Lightning impulse withstand

75KV

125 kV

185 kV

200 kV

Power frequency withstand(wet 1min)

35KV

55 kV

80 kV

90 kV